Toroidal transformers to associate with differential relays

Diameter
  • 35 mm
  • 60 mm
  • 80 mm
  • 110 mm
  • 160 mm
  • 210 mm

 

Toroidal current transformers

Relationship; 50 / 0,1

Number of turns: 500 Included terminal cover

Assembly tips:

- Put the cables in the center of toroidal

- It should not be placed close to a curved area of the cables that crossed it

- Use a toroid of at least twice the diameter of the cable or braid of the cables

- In very critical cases, it is necessary to install a ferromagnetic sleeve around the cables on the internal part of the toroidal

- The toroidal must be crossed in the same sense by all cables (included in neutral if present)

- The neutral cable should not be connected to ground after toroidal

- In case the protected line has a metallic protection, it must be grounded after toroidal.

The toroid connection to the leakage relay must be connected with a shielded cable in the following cases:

- Differential threshold

- Distance from toroidal> 10 m

- Signal cable installed less than 30 cm from the power cord

It is advisable, and in mandatory critical situations:

- Make a braid with toroidal-relay connection cables

- The cable section should not be less than 1 mm and its length can not exceed 20 m

- The cables can not be installed near electronic components or power cords that can generate magnetic fields or disturbances in the measurement signal